ES-50CU EN54

TONTECHNIKA ES-50CU EN54 is EN54-16 certified 6 zone voice alarm system controller which is designed for public address and voice alarm system, all main signal will be monitored, built-in 500W amplifier, voice alarm controller, 8 zone paging controller, speaker line monitoring and amplifier changeover.

Deskripsi

The TONTECHNIKA ES-50CU EN54 voice evacuation controller is EN54-16 certified public address & voice evacuation system. The all in one voice alarm & evacuation controller built-in remote PC software, zone paging controller, all main signal line monitoring, amplifier changeover, speaker line supervision, power supply monitoring and power amplifier, voice recorder, SD card, emergency microphone and fire alarm interface. The voice evacuation controller is innovated with DSP (digital signal processor) to ensure its hi-fi audio performance and superior signal processing in case of commercial announcement and emergency evacuation. Each controller built-in 6 zone speaker outputs, rated power output at 500W. The voice evacuation controller shall be pre-set through the supplied software over microphone number, zone number, zone loading, speaker monitoring, fire alarm mode, alert/EVAC message zone output, AC/DC etc, then synchronized the setting to master controller and router. The voice evacuation system is strictly follow the Construction products Regulation(EU)No 305/2011: EN54-16:2008 Voice Alarm Control and Indicating Equipment.

 

Features

  • EN54-16 certification No. I/ISEETC. 000620190305.
  • Digital voice evacuation system all in one controller.
  • Integration of voice evacuation controller, remote PC software, zone paging controller, all main signal line monitoring, amplifier changeover, speaker line supervision, power supply monitoring and power amplifier, voice recorder, SD card, emergency microphone and fire alarm interface.
  • Auto broadcasting EVAC and alert 256 voice messages to pre-set zones.
  • Customized alert, evacuation & business message stored at SD card.
  • AB speaker line surveillance to avoid any speaker line failure.
  • Back-up power amplifier management.
  • Up to 120 zones by cascaded more router.
  • Support 32 units of remote paging microphone ES-50RM EN54.
  • Support external connection of fireman microphone ES-50FM EN54.
  • Support of touch screen microphone.
  • Redundant network cabling backup through CAT6 cable loop connection.
  • 8 supervised control inputs & 8 control outputs, 1 fault, 1 reset & 1 EVAC relay outs.
  • Logs and fault events auto recording.

 

Spesifikasi

ModelES-50CU EN54
Description6 Zone Voice Evacuation Controller
Rated Power Output500W
Fireman Microphone5Mv, 600Ω
Line 1-2 Inputs385mV, 10kΩ balanced Combo XLR
Line 3-6 Inputs350mV, 10kΩ, RCA
Frequency Response80Hz~20kHz
THD<1% at RMS,1KHz
S/N Ratio>70dB
Speaker Output100V AB 6 zone speaker outputs
REC Output200mV
Control Input & Output8 control inputs: Max 3.3V (voltage mode) or 0V closed contact;

8 control outputs: 0V closed contact;

1 fault, 1 reset & 1 EVAC relay outs

Voice MessageMP3 or WMA format, two separate players of SD card, programmable voice message up to 256, 10 years valid
Event RecordHEX format, Hard Flash memory, events up to 1000 records, 10 years valid
Operation TempOperation Temp: +5℃ ~ +40℃; Store Temp: -20℃ ~ +70℃; Humidity: <95%
Power Consumption650W
Power SupplyAC230V or 115V & 24V DC inputs, 50-60HZ
AC Fuse250V/6.3A, slow type and restorable fuse
Dimension484×132×405mm
Weight11.2kg